Overhead Cable
- Product Description
-
1. Product Standard: GB/T14049-2008
2. Application: This product is suitable for copper core, aluminum core, and aluminum alloy core weather-resistant overhead cables insulated with high-density polyethylene and cross-linked polyethylene for AC rated voltage of 10kV and below overhead power lines.
3. Usage Characteristics
Cable conductor long-term allowable operating temperature: High-density polyethylene insulation should not exceed 75℃; cross-linked polyethylene insulation should not exceed 90℃.
The ambient temperature for cable laying should not be lower than -20℃.
The allowable bending radius of the cable should not be less than the diameter of the cylindrical body used in the cable bending test.
4. Model and SpecificationsModel Name Specification Application Number of Cores Cross-section mm² JKYJ Copper Core Cross-linked Polyethylene Insulated Overhead Cable 1, 3
3+K(A)
3+K(B)10~400 For overhead fixed laying, soft copper core products are used for
Transformer lead-down wires.
When laying cables, consideration should be given to maintaining a certain distance between cables and trees; during cable operation, frequent contact between cables and trees is allowed.JKTRYJ Soft Copper Core Cross-linked Polyethylene Insulated Overhead Cable 25~400 JKLYJ Aluminum Core Cross-linked Polyethylene Insulated Overhead Cable 25~400
Among them K25~120JKLHYJ Aluminum Alloy Core Cross-linked Polyethylene Insulated Overhead Cable JKY Copper Core Polyethylene Insulated Overhead Cable 1 10~400 JKTRY Soft Copper Core Polyethylene Insulated Overhead Cable Model Name Specification Application Number of Cores Cross-section mm² JKLY Aluminum Core Polyethylene Insulated Overhead Cable 1 10~400 Same as above JKLHY Aluminum Alloy Core Polyethylene Insulated Overhead Cable JKLYJ/B Aluminum Core Natural Color Cross-linked Polyethylene Insulated Overhead Cable 3 25~400 Overhead fixed laying.
When laying cables, consideration should be given to maintaining a certain distance between cables and trees; during cable operation, frequent contact between cables and trees is allowed.JKLHYJ/B Aluminum Alloy Core Natural Color Cross-linked Polyethylene Insulated Overhead Cable 3+K(A)
3+K(B)25~400
Among them K25~120JKLYJ/Q Aluminum Core Lightweight Cross-linked Polyethylene Thin Insulated Overhead Cable 1 10~400 Overhead fixed laying.
When laying cables, consideration should be given to maintaining a certain distance between cables and trees; during cable operation, only short-term contact between cables and trees is allowed.JKLHYJ/Q Aluminum Alloy Core Lightweight Cross-linked Polyethylene Thin Insulated Overhead Cable JKLY/Q Aluminum Core Lightweight Polyethylene Thin Insulated Overhead Cable JKLHY/Q Aluminum Alloy Core Lightweight Polyethylene Thin Insulated Overhead Cable Note:
1. Among them, K is the load-bearing stranded wire. According to engineering design needs, the specified cross-section can be selected to match the corresponding conductor cross-section. If a larger tower span uses an additional load-bearing cable, this load-bearing cable is not included in the cable structure.
2. (A) indicates steel load-bearing stranded wire, (B) indicates aluminum alloy load-bearing stranded wire.
Keywords:
Related Products
Get a Quote